From 09e4e5ca344c0c7d668560528567dca6e3fd47f4 Mon Sep 17 00:00:00 2001 From: Matt Steen Date: Thu, 4 Jan 2024 15:10:28 -0700 Subject: [PATCH] Delete 2021/4.2.json --- 2021/4.2.json | 56 --------------------------------------------------- 1 file changed, 56 deletions(-) delete mode 100644 2021/4.2.json diff --git a/2021/4.2.json b/2021/4.2.json deleted file mode 100644 index 1dcad5a..0000000 --- a/2021/4.2.json +++ /dev/null @@ -1,56 +0,0 @@ -{ - "section": "4.2", - "name": "VAV Terminal Unit with Reheat", - "data": { - "VAV box damper position": { - "Required?": "R", - "Type": "AO\nOR\ntwo DOs ", - "Device": "Modulating actuator\nOR\nFloating actuator " - }, - "Heating signal": { - "Required?": "R", - "Type": "AO \nOR\ntwo DOs ", - "Device": "Modulating valve\nOR\nFloating actuator \nOR\nModulating electric heating coil" - }, - "Discharge airflow": { - "Required?": "R", - "Type": "AI", - "Device": "DP transducer connected to flow sensor" - }, - "Discharge air temperature (DAT)": { - "Required?": "R", - "Type": "AI", - "Device": "Duct temperature sensor (probe or averaging at designer\u2019s discretion)" - }, - "Zone temperature": { - "Required?": "R", - "Type": "AI", - "Device": "Room temperature sensor" - }, - "Local override (if applicable)": { - "Required?": "A", - "Type": "DI", - "Device": "Zone thermostat override switch" - }, - "Occupancy sensor (if applicable)": { - "Required?": "A", - "Type": "DI", - "Device": "Occupancy sensor " - }, - "Window switch (if applicable)": { - "Required?": "A", - "Type": "DI", - "Device": "Window switch" - }, - "Zone temperature setpoint adjustment\n(if applicable)": { - "Required?": "A", - "Type": "AI", - "Device": "Zone thermostat adjustment" - }, - "Zone CO2 level (if applicable)": { - "Required?": "A", - "Type": "AI", - "Device": "Room CO2 sensor" - } - } -}