When daisy-chaining chassis together, GB is the uplink port and STK is the stacking (cable consolidation) port. Connect the GB ports to the management network or to the STK port of CMC in a chassis that is closer to the network. You must connect the STK port only to a GB port further from the chain or network.
Using the LCD panel on the front of the system, provide CMC with a static IP address or configure it for DHCP.
Connect KVM, which talks to CMC. Login with root/calvin, and then enter:
racadm setniccfg -s 192.168.1.254 255.255.255.0 192.168.1.1
You can then access the web browser and login with root/calvin: https://192.168.1.254 (or https://127.0.0.1:2000/cgi-bin/webcgi/login if tunneled).
Set the root password for chassis management controller. Chassis Overview [left menu] > User Authentication [top tab] > Local Users [sub menu] > Click on "1" [button on "root" row].
- Check "Change password"
- Enter Password (twice)
Then go to Server Overview [left menu] > Setup [top tab] > iDrac [sub menu] > Quick Deploy Settings [below top menu].
- Quick Deploy Enabled: checked
- Enable iDRAC LAN: checked
- Enable iDRAC IPv4: checked
- Enable iDRAC IPMI over LAN: checked
- Starting iDRAC IPv4 Address (Slot 1): 192.168.1.212
- iDRAC IPv4 Netmask: 255.255.255.0
- iDRAC IPv4 Gateway: 192.168.1.1
Click Save QuickDeploy Settings
.
Below, click Auto-Populate Using QuickDeploy Settings
At bottom, click Apply iDRAC Network Settings
to apply them to existing blades.
Select Chassis Overview > Power > Control. This will power on the chassis when you click Apply. This powers on the MXL as well.
You must enable 110v operation, or the blades won't boot.
You can do this from the web interface:
Chassis Overview > Power > Configuration > Allow 110 VAC Operation > apply
Or ssh:
ssh root@ac1
Then Dell PowerEdge M1000e Chassis Management Controller Firmware (p215)
racadm config -g cfgChassisPower -o cfgChassisAllow110VACOperation 1
Verify that it was set:
$ racadm getconfig -g cfgChassisPower
# cfgChassisInPower=373 W (1272 BTU/h)
# cfgChassisPeakPower=813 W
# cfgChassisPeakPowerTimestamp=16:29:46 12/19/2015
# cfgChassisMinPower=88 W
# cfgChassisMinPowerTimestamp=19:46:33 12/18/2015
# cfgChassisPowerStatus=3
# cfgChassisRedundantState=1
cfgChassisPowerCap=16685 W
cfgChassisPowerCapF=16685 W
cfgChassisPowerCapBTU=56931 BTU/h
cfgChassisPowerCapFBTU=56931 BTU/h
cfgChassisPowerCapPercent=100 %
cfgChassisPowerCapFPercent=100 %
cfgChassisRedundancyPolicy=1
cfgChassisDynamicPSUEngagementEnable=0
# cfgChassisInMaxPowerCapacity=4328 W
# cfgChassisInRedundancyReserve=4328 W
# cfgChassisInPowerServerAllocation=256 W
# cfgChassisInfrastructureInPowerAllocation=229 W
# cfgChassisTotalInPowerAvailable=7587 W
# cfgChassisStandbyInPowerCapacity=0 W
# cfgChassisPowerClear=******** (Write-Only)
# cfgChassisPowerClearTimestamp=19:41:17 12/18/2015
cfgChassisPowerButtonEnable=1
cfgChassisAllow110VACOperation=16:13:19 12/19/2015
cfgChassisMaxPowerConservationMode=0
cfgChassisPerformanceOverRedundancy=1
# cfgSystemEnergyConsumptionClear=******** (Write-Only)
cfgChassisServerBasedPowerMgmtMode=0
http://tech.ryancox.net/2010/12/useful-commands-for-dell-servers.html
get BIOS.BiosBootSettings.HddSeq
set BIOS.BiosBootSettings.HddSeq Disk.SDInternal.1-1,RAID.Integrated.1-1
jobqueue create BIOS.Setup.1-1
serveraction hardreset
Sets up DSU repo http://linux.dell.com/repo/hardware/dsu. This how to setup racadm on Linux:
yum install openssl098e.x86_64
curl -L -s -S http://linux.dell.com/repo/hardware/latest/bootstrap.cgi | bash
Need to figure out if we should enable this or cfgChassisServerBasedPowerMgmtMode=0
Connect to the DRAC of an m620:
$ ssh root@a14c
root@a14c's password:
/admin1-> racadm
racadm>>racreset
RAC reset operation initiated successfully. It may take a few
minutes for the RAC to come online again.
racadm>>exit
/admin1->exit
Watch for the DRAC to come back up:
$ ping a14c
Make sure server is booted:
serveraction powerstatus
You can autocomplete many commands. Not all values, though.
RACADM Command Line Reference Guide iDRAC7 (p278):
set iDRAC.IPMILan.Enable 1
Optionally:
set iDRAC.IPMILan.AlertEnable 1
These command are committed immediately. The next ones require a "job queue".
RACADM Command Line Reference Guide iDRAC7 (p376):
set BIOS.SerialCommSettings.ConTermType Vt100Vt220
set BIOS.SerialCommSettings.RedirAfterBoot Enabled
set BIOS.SerialCommSettings.SerialPortAddress Com1
set BIOS.SerialCommSettings.SerialComm OnConRedir
set BIOS.SerialCommSettings.FailSafeBaud 115200
http://jonamiki.com/2014/10/18/racadm-change-bios-settings-create-commit-job-reboot-and-apply/ This command takes awhile:
jobqueue create BIOS.Setup.1-1 -r pwrcycle -s TIME_NOW -e TIME_NA
Check status:
jobqueue view
???? WHy doesn't job get executed on a14c?
Verify that it is set:
racadm>>get BIOS.SerialCommSettings
racadm get BIOS.SerialCommSettings
[Key=BIOS.Setup.1-1#SerialCommSettings]
ConTermType=Vt100Vt220
FailSafeBaud=115200
RedirAfterBoot=Enabled
SerialComm=OnConRedir
SerialPortAddress=Com1
racadm>>get iDRAC.IPMILan
racadm get iDRAC.IPMILan
[Key=iDRAC.Embedded.1#IPMILan.1]
AlertEnable=Disabled
CommunityName=public
Enable=Enabled
EncryptionKey=0000000000000000000000000000000000000000
PrivLimit=4
https://wiki.nikhef.nl/grid/Serial_Consoles Make sure the window is 80x25.
$ ipmitool -v -I lanplus -H 192.168.1.213 -U root -f ~/password sol activate
Clear all jobs:
jobqueue delete -i JID_CLEARALL_FORCE
This does not work in all cases: jobqueue delete --all
http://thornelabs.net/2014/04/16/dell-idrac-racadm-commands-and-scripts.html
https://www.thomas-krenn.com/en/wiki/Deactivate_IPMI_NONE_Authentication_Type
http://www.gooksu.com/2015/04/27/racadm-quick-dirty-cheatsheet/
- cmc FBRZDZ1 (firmware 4.3.1)
- slot 2 GV3VFZ1
- 3 GV4TFZ1
- 4 GV3WFZ1
- 5 GV3TFZ1
Tin's Journey iDRAC 7 CheatSheet
https://confluence.liskl.com/display/LDC/iDRAC+7+CheatSheet+with+racadm
https://github.com/hurulu/idrac-configure-script/blob/master/idrac_configure.sh
https://wikitech.wikimedia.org/wiki/Platform-specific_documentation/Dell_PowerEdge_RN10
http://comments.gmane.org/gmane.linux.hardware.dell.poweredge/37580
https://github.com/hurulu/idrac-configure-script/blob/master/idrac_configure.sh
accessibility java viewer
map dvd with an iso
bios
racadam order
start.html and other pages hardwired with absolute redirects
getting caught with reboot, order of mods (need disks)
Map CD
lack of errors on boot
VNC requires enterprise license
setup serial on linux
ext4
swap didn't work? (see screenshot) create partition after?
virtual media